Vaisala HMD60 Series Duct Humidity and Temperature Transmitter
Description
The duct-mounted HMD60 series uses the latest-generation HUMICAP® R2 sensor with improved corrosion resistance, in a cast-aluminium IP66 housing. It is built for supply and return air ducts, air handlers and CRAH discharge where measurement accuracy and native BMS integration matter.
Key features
- Accuracy up to ±1.5 %RH and ±0.1 °C
- HMD62 (4 … 20 mA), HMD65 (0 … 10 V plus BACnet MS/TP and Modbus RTU), TMD62 temperature-only
- All common humidity parameters: dew point, enthalpy, wet bulb, absolute humidity, mixing ratio
- Resistant to chemicals and dust; IP66 (NEMA 4X)
- Traceable calibration certificate; field adjustment with quick access to electronics
- Compatible with Vaisala Insight PC software
Models
| HMD62 | RH+T, 2 × 4 … 20 mA |
|---|---|
| HMD65 | RH+T, 2 × 0 … 10 V + RS-485 BACnet MS/TP / Modbus RTU |
| TMD62 | T-only, 1 × 4 … 20 mA |
| HMD60 / TMD60 | Configurable outputs and scale, short probe option |
Riajati supplies Vaisala instruments in Malaysia — send us your measurement points, required outputs and quantities through the Enquiry tab for a quotation.
| Relative humidity | |
|---|---|
| Measurement range | 0 … 100 %RH |
| Accuracy 0 … +40 °C | ±1.5 %RH (0 … 90 %RH), ±2.5 %RH (90 … 100 %RH) |
| Accuracy −40 … 0 °C, +40 … +80 °C | ±2.5 %RH (0 … 90 %RH), ±3.5 %RH (90 … 100 %RH) |
| Stability (typical HVAC) | ±0.5 %RH/year |
| Response time (T63, +20 °C) | 15 s |
| Sensor options | HUMICAP® R2; HUMICAP® 180V (catalytic, for H₂O₂) |
| Temperature | |
| Measurement range | −40 … +80 °C |
| Accuracy at +20 °C | ±0.1 °C |
| Sensor | Pt1000 RTD Class F0.1, IEC 60751 |
| Inputs and outputs | |
| HMD62 / TMD62 supply | 10 … 35 VDC (0 Ω), 20 … 35 VDC (600 Ω) |
| HMD65 supply | 15 … 35 VDC or 16 … 24 VAC, 1.0 W typical |
| Digital (HMD65) | Isolated RS-485; BACnet MS/TP (address 0 … 127) and Modbus RTU (1 … 247) |
| Service port | M8 4-pin — HM70 handheld or Insight PC software |
| Environment and mechanics | |
| Operating temperature, electronics | −40 … +60 °C |
| Operating temperature, probe | −40 … +80 °C |
| Max. flow speed | 50 m/s with sintered filter |
| Housing / probe | Cast aluminium / stainless steel |
| IP rating | IP66 (NEMA 4X) |
| Weight | 511 g |







Reviews